A CFD study for evaluating the effects of natural ventilation on indoor comfort conditions

  • Received: 10 December 2016 Accepted: 05 March 2017 Published: 17 March 2017
  • There is an increasing interest in improving energy efficiency in buildings due to the increased awareness about environmental impact and energy cost. Natural ventilation is an environmentally friendly technique which has become more attractive way for reducing energy use while it also provides acceptable comfort conditions. The research shows a case study building in which the natural ventilation effect due to wind-driven forces on indoor comfort conditions is evaluated. Moreover, the architectural solutions selected during the building design phase to improve the natural ventilation behaviour are successfully validated in a full-scale building. The indoor comfort conditions are evaluated through contrasted performance indicators: draught risk (DR), predicted percentage of dissatisfied people (PPD) and predicted mean vote (PMV) indexes. The results show that air movement due to natural ventilation allows increasing indoor air temperature maintaining the initial comfort conditions. Therefore, the mechanical air conditioning use can be postponed until the indoor air temperature is high and would, consequently, reduce the total building energy consumption. Thereby, a proper natural ventilation focus during the initial design stage could improve the building energy efficiency without compromising the indoor comfort conditions.

    Citation: Miguel Mora-Pérez, Ignacio Guillen-Guillamón, Petra Amparo López-Jiménez. A CFD study for evaluating the effects of natural ventilation on indoor comfort conditions[J]. AIMS Environmental Science, 2017, 4(2): 289-309. doi: 10.3934/environsci.2017.2.289

    Related Papers:

  • There is an increasing interest in improving energy efficiency in buildings due to the increased awareness about environmental impact and energy cost. Natural ventilation is an environmentally friendly technique which has become more attractive way for reducing energy use while it also provides acceptable comfort conditions. The research shows a case study building in which the natural ventilation effect due to wind-driven forces on indoor comfort conditions is evaluated. Moreover, the architectural solutions selected during the building design phase to improve the natural ventilation behaviour are successfully validated in a full-scale building. The indoor comfort conditions are evaluated through contrasted performance indicators: draught risk (DR), predicted percentage of dissatisfied people (PPD) and predicted mean vote (PMV) indexes. The results show that air movement due to natural ventilation allows increasing indoor air temperature maintaining the initial comfort conditions. Therefore, the mechanical air conditioning use can be postponed until the indoor air temperature is high and would, consequently, reduce the total building energy consumption. Thereby, a proper natural ventilation focus during the initial design stage could improve the building energy efficiency without compromising the indoor comfort conditions.


    加载中
    [1] Kudryashova A, Genkov A, Mo T (2015) Certification schemes for sustainable buildings: assessment of BREEAM, LEED and LBC from a strategic sustainable development perspective. Blekindge Institute of Technology, Karlskrona.
    [2] Taleb HM (2015) Natural ventilation as energy efficient solution for achieving low-energy houses in Dubai. Energy Build 99: 284-291. doi: 10.1016/j.enbuild.2015.04.019
    [3] U.E. Environmental Protection Agency (EPA), Green building basic information, 2014. Available from: http://www.epa.gov/greenbuilding/pubs/about.htm.
    [4] Luo ZW, Zhao JN, Gao J, et al. (2007). Estimating natural-ventilation potential considering both thermal comfort and IAQ issues. Build Environ 42: 2289-2298. doi: 10.1016/j.buildenv.2006.04.024
    [5] Hitchin ER, Wilson CB (1967) A review of experimental techniques for the investigation of natural ventilation in buildings. Build Sci 2: 59-82. doi: 10.1016/0007-3628(67)90007-2
    [6] Chen Q (2009) Ventilation performance prediction for buildings: A method overview and recent applications. Build Environ 44: 848-858. doi: 10.1016/j.buildenv.2008.05.025
    [7] Coakley D, Raftery P, Keane M (2014) A review of methods to match building energy simulation models to measured data. Renew Sustain Energy Rev 37: 123-141. doi: 10.1016/j.rser.2014.05.007
    [8] Zhu YX, Luo MH, Ouyang Q, et al. (2015) Dynamic characteristics and comfort assessment of airflows in indoor environments: A review. Build Environ 91: 5-14. doi: 10.1016/j.buildenv.2015.03.032
    [9] Etheridge D (2015) A perspective on fifty years of natural ventilation research. Build Environ 91: 51-60. doi: 10.1016/j.buildenv.2015.02.033
    [10] Wang H, Lin H, Ng VCY, et al. (2015) Failure of natural ventilation strategy in a sustainable house in China. Int J Low-Carbon Tech 10: 216-228. doi: 10.1093/ijlct/ctt035
    [11] Moosavi L, Mahyuddin N, Abghafar N, et al. (2014) Thermal performance of atria: an overview of natural ventilation effective designs. Renew Sustain Energy Rev 34: 654-670. doi: 10.1016/j.rser.2014.02.035
    [12] Foucquier A, Robert S, Suard F, et al. (2013) State of the art in building modelling and energy performances prediction: A review. Renew Sustain Energy Rev 23: 271-288.
    [13] Mora-Pérez M, Guillén-Guillamón I, López-Jiménez PA (2015) Computational analysis of wind interactions for comparing different buildings sites in terms of natural ventilation. Adv Eng Softw 88: 73-82. doi: 10.1016/j.advengsoft.2015.06.003
    [14] Sun YM, Zhang WY, Zhang CY (2014) Preliminary study on natural ventilation for hospital building in hot and humid regions. 30th International Plea Conference. CEPT University, Ahmedabad.
    [15] Zhou CB, Wang ZQ, Chen QY, et al. (2014) Design optimization and field demonstration of natural ventilation for high-rise residential buildings. Energy Build 82: 457-465. doi: 10.1016/j.enbuild.2014.06.036
    [16] Van Hooff T, Blocken B, Aanen L, et al. (2011) A venturi-shaped roof for wind-induced natural ventilation of buildings: wind tunnel and CFD evaluation of different design configurations. Build Environ 46: 1797-1807. doi: 10.1016/j.buildenv.2011.02.009
    [17] Liu PC, Lin HT, Chou JH (2009) Evaluation of buoyancy-driven ventilation in atrium buildings using computational fluid dynamics and reduced-scale air model. Build Environ 44: 1970-1979. doi: 10.1016/j.buildenv.2009.01.013
    [18] Hughes BR, Calautit JK, Ghani SA (2012) The development of commercial wind towers for natural ventilation: A review. Appl Energy 92: 606-627. doi: 10.1016/j.apenergy.2011.11.066
    [19] Mora-Pérez M, Guillén-Guillamón I, López-Patiño G, et al. (2016) Natural ventilation building design approach in Mediterranean regions-A case study at the Valencian coastal regional scale (Spain). Sustain 8: 855. doi: 10.3390/su8090855
    [20] ISO Standard 7730 (2005) Ergonomics of the thermal environment-Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria.
    [21] AENOR (2008) AEN/CTN 100. UNE-CR 1752:2008. Ventilation for buildings-Design criteria for the indoor environment. Comité técnico, Spain. Available from: http://www.aenor.es.
    [22] ANSI/ASHRAE (2013) Thermal environmental conditions for human occupancy.
    [23] Gagliano A, Nocera F, Patania F, et al. (2016) Synergic effects of termal mass and natural ventilation on the termal behaviour of traditional massive buildings. Int J Sustain Energy 35: 411-428. doi: 10.1080/14786451.2014.910517
    [24] CD-Adapco. Star CCM+ User's Manual. Available from: www.cd-adapco.com.
    [25] Franke J, Hellsten A, Schlünzen H, et al. (2007) Best practice guideline for the CFD simulation of flows in the urban environment. Cost Off Bruss 44:1-52.
    [26] Wieringa J (1992) Updating the Davenport roughness classification. J Wind Eng Ind Aerodyn 41: 357-368. doi: 10.1016/0167-6105(92)90434-C
    [27] Agencia Estatal de Meteorología de España (AEMET). Spanish State Meteorological Agency, Ministry of Agriculture and Fisheries, Food and Environment. Available from: http://www.aemet.es.
    [28] Windfinder. Available from: http://es.windfinder.com/windstats/windstatistic_valencia.htm.
    [29] Manwell, JF, Mcgowan, JG, Rogers, AL (2009) Wind energy explained: theory, design and application, 2 Eds., Wiley.
    [30] Peterson EW, Hennessey JP (1977) On the use of power laws for estimates of wind power potential. J Appl Meteorol 17.
    [31] Justus CG, Mikhail A (1976) Height variation of wind speed and wind distributions statistics. Geophys Res Lett 3: 261-264. doi: 10.1029/GL003i005p00261
    [32] Ray SD, Gong NW, Glicksman LR, et al. (2014) Experimental characterization of full-scale naturally ventilated atrium and validation of CFD simulations. Energy Build 69: 285-291. doi: 10.1016/j.enbuild.2013.11.018
    [33] Shao JT, Liu J, Zhao JN (2012) Evaluation of various non-linear k-epsilon models for predicting wind flow around an isolated high-rise building within the surface boundary layer. Build Environ 57: 145-155. doi: 10.1016/j.buildenv.2012.04.018
    [34] García JAO, (2010) A review of general and local thermal comfort models for controlling indoor ambiences, In: Kumar, A. Author, Air Quality, InTech, 309-326.
    [35] Fanger, PO (1972) Thermal comfort-Analysis and applications in environmental engineering, Kingsport Press.
    [36] Reglamento de Instalaciones Térmicas en los Edificios (RITE). Ministerio de Industria, Energía y Turismo, Gobierno de España. Available from: http://www.minetur.gob.es/energia/desarrollo/EficienciaEnergetica/RITE/Paginas/InstalacionesTermicas.aspx.
    [37] EN 13779:2007. Ventilation for non-residential buildings-Performance requirements for ventilation and room-conditioning systems. April 2007.
    [38] Hajdukievwicz M, Geron M, Keane MM (2013) Formal calibration methodology for CFD models of naturally ventilated indoor environments. Build Environ 59: 290-302. doi: 10.1016/j.buildenv.2012.08.027
    [39] Van Hooff T, Blocken B (2010) On the effect of wind direction and urban surroundings on natural ventilation of a large semi-enclosed stadium. Comput Fluids 39: 1146-1155. doi: 10.1016/j.compfluid.2010.02.004
    [40] Lo LJ, Novoselac A (2012) Cross ventilation with small openings: Measurements in a multi-zone test building. Build Environ 57: 377-386. doi: 10.1016/j.buildenv.2012.06.009
    [41] Franke J, Hirsch C, Jensen AG, et al. (2004) Recommendations on the use of CFD in wind engineering. In: van Beeck, J.P.A.J. (Ed.), Proceedings of the International Conference Urban Wind Engineering and Building Aerodynamics, von Karman Institute.
  • Reader Comments
  • © 2017 the Author(s), licensee AIMS Press. This is an open access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0)
通讯作者: 陈斌, bchen63@163.com
  • 1. 

    沈阳化工大学材料科学与工程学院 沈阳 110142

  1. 本站搜索
  2. 百度学术搜索
  3. 万方数据库搜索
  4. CNKI搜索

Metrics

Article views(5333) PDF downloads(998) Cited by(0)

Article outline

Figures and Tables

Figures(16)  /  Tables(1)

/

DownLoad:  Full-Size Img  PowerPoint
Return
Return

Catalog